Decisive Engineering
Home Services Expertise Learn Glossary Contact Us

Reference

Glossary

Every technical term used in the arc-flash and TCC tutorials, with a one-paragraph definition and links to related concepts. Filter by term name or definition text; clicking a related-term chip jumps to that entry within this page.

35 of 35 terms

TermDefinitionRelated
ANSI transformer damage curveA through-fault withstand envelope published by ANSI/IEEE C57.109. Defines how long a transformer can safely carry a given multiple of its FLA before mechanical or thermal damage. Plotted on a TCC, upstream protective devices must clear below this envelope.
  • Time-current curve (TCC)
  • ICEA cable damage curve
Arc ratingA clothing system's tested ability (in cal/cm²) to attenuate an arc-flash thermal exposure before second-degree skin burns occur underneath. Determined by ASTM F1959 testing. Must equal or exceed the worker's incident-energy exposure at the working distance.
  • Incident energy (IE)
  • PPE category
  • NFPA 70E
Arc-flash boundary (AFB)The distance from the prospective arc source at which incident energy drops to 1.2 cal/cm² — the onset threshold for second-degree skin burns. Inside the AFB, anyone present must wear arc-rated PPE or be physically excluded.
  • Incident energy (IE)
  • Working distance (WD)
  • PPE category
Arcing current (Iarc)The actual RMS current that flows when an arcing fault is in progress, lower than Ibf because the arc plasma adds impedance. Arc-flash energy is driven by Iarc, not Ibf — and Iarc tracks Ibf nonlinearly, so a lower bus Ibf can still produce damaging energy.
  • Bolted-fault current (Ibf)
  • Incident energy (IE)
  • IEEE 1584
  • Electrode configuration (VCB / VCBB / HCB)
ARMS / RELT (maintenance switching)Vendor names for energy-reducing maintenance switching: a switch on an upstream breaker that temporarily makes its instantaneous element fast (or activates a lower pickup) while a worker is in front of downstream equipment. Method 3 of the six in NEC 240.87.
  • NEC 240.87
  • Instantaneous trip (INST)
  • Short-time delay (S)
  • Zone-selective interlocking (ZSI)
  • Incident energy (IE)
Bolted-fault current (Ibf)The symmetric RMS short-circuit current that would flow if the fault were a zero-impedance metallic connection between conductors. The worst-case bus fault current — used to size breaker AIC ratings and as the starting input to arc-flash math.
  • Arcing current (Iarc)
  • X/R ratio
  • Incident energy (IE)
Breaker AIC ratingAmpere Interrupting Capacity — the maximum symmetrical RMS fault current a breaker is rated to interrupt without mechanical damage or loss of insulation. Standard ratings: 14, 22, 35, 42, 65, 100, 200 kAIC at 480 V. The available Ibf at the breaker location must be below its AIC.
  • Bolted-fault current (Ibf)
  • X/R ratio
  • Fuse class (RK5 / J / L / T)
  • Current-limiting fuse
Current-limiting fuseA fuse class designed to interrupt within the first sub-cycle of a high-magnitude fault, truncating the peak current before it reaches the prospective Ibf. Class J and Class L fuses are current-limiting; RK5 is not. Sub-8 ms clearing in the current-limiting region.
  • Fuse class (RK5 / J / L / T)
  • Breaker AIC rating
  • NEC 240.67
  • Incident energy (IE)
Differential relayingA protection scheme that compares current entering a zone (transformer, bus, generator) with current leaving. If the difference exceeds a threshold, the relay trips on the assumption that the missing current is being drawn by an in-zone fault. Method 2 of NEC 240.87.
  • NEC 240.87
  • Zone-selective interlocking (ZSI)
  • Selective coordination
Electrode configuration (VCB / VCBB / HCB)How the arcing electrodes are oriented inside the enclosure, controlling how much arc energy bounces back toward the worker. VCB = vertical conductors in a box; VCBB = vertical conductors with a barrier behind; HCB = horizontal conductors in a box.
  • IEEE 1584
  • Arcing current (Iarc)
  • Incident energy (IE)
Fuse class (RK5 / J / L / T)A UL-defined family of low-voltage fuse types with distinct physical dimensions, interrupting ratings, and time-current characteristics. RK5 is the legacy general-purpose class; Class J is faster and more current-limiting; Class L covers 601–6000 A; Class T is compact and ultra-fast.
  • Time-current curve (TCC)
  • Selective coordination
ICEA cable damage curveAn I²t-based withstand curve for insulated power cable, derived from ICEA P-32-382. Defines how long the cable can carry a given fault current before its insulation reaches a temperature that permanently damages it.
  • Time-current curve (TCC)
  • ANSI transformer damage curve
IEEE 1584The empirical regression standard that converts system parameters (voltage, bolted Isc, gap, electrode geometry, working distance, clearing time, grounding) into incident energy and arc-flash boundary. The 2002 and 2018 editions are both in use; this tutorial implements 2002.
  • Incident energy (IE)
  • Arcing current (Iarc)
  • Electrode configuration (VCB / VCBB / HCB)
  • NFPA 70E
Incident energy (IE)The thermal energy per unit area that a worker at the working distance would receive during an arc-flash event, expressed in cal/cm². Drives the arc-rating requirement of the PPE the worker must wear.
  • Arcing current (Iarc)
  • Working distance (WD)
  • Arc-flash boundary (AFB)
  • PPE category
  • IEEE 1584
Inrush currentThe high-magnitude, short-duration current that flows when a transformer or motor is first energized. Transformer magnetizing inrush peaks at 8–12× FLA and decays over a few cycles; motor starting inrush is 5–7× FLA and lasts seconds.
  • ANSI transformer damage curve
  • Long-time pickup (L)
  • Instantaneous trip (INST)
  • Motor contribution
Instantaneous trip (INST)A high-current pickup setting that trips a breaker with no intentional delay — typically one cycle (~16 ms) plus mechanical opening time. Provides fast arc-flash energy reduction at high fault currents but limits selective coordination with downstream devices.
  • Time-current curve (TCC)
  • Short-time delay (S)
  • LVPCB-LSI
  • Selective coordination
Long-time pickup (L)The current threshold above which a breaker's long-time delay region starts timing toward a trip. Usually expressed as a multiple of sensor rating (e.g. 0.9× = 90 % of sensor). Sets where the inverse-time region of the TCC begins.
  • Time-current curve (TCC)
  • Short-time delay (S)
  • Instantaneous trip (INST)
  • LVPCB-LSI
LVPCB-LSILow-Voltage Power Circuit Breaker with Long-time, Short-time, and Instantaneous trip elements — the three-region adjustable protection used at service mains and large feeders in switchgear. LSIG adds a ground-fault element.
  • Time-current curve (TCC)
  • Long-time pickup (L)
  • Short-time delay (S)
  • Instantaneous trip (INST)
  • Selective coordination
Motor contributionThe fault current that running motors deliver into a downstream fault during the first few cycles. Motors act as generators behind their subtransient reactance, pumping current backward into the fault until the rotor decays. Standard lumped estimate: 4× connected motor FLA.
  • Bolted-fault current (Ibf)
  • Breaker AIC rating
  • Inrush current
NEC 110.16The label-content section of the National Electrical Code. Requires field-marked arc-flash warning labels on switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers likely to be examined or maintained while energized.
  • NFPA 70E
  • Incident energy (IE)
  • Arc-flash boundary (AFB)
  • PPE category
  • Working distance (WD)
NEC 240.67The fuse-side companion to NEC 240.87. Requires arc-flash energy reduction methods on fuses rated 1200 A or larger. Acceptable methods include current-limiting fuse selection or differential / arc-energy reduction relaying.
  • NEC 240.87
  • Fuse class (RK5 / J / L / T)
  • Current-limiting fuse
NEC 240.87A National Electrical Code requirement that breakers 1200 A or larger with adjustable trip have at least one of six listed arc-flash reduction features active, addressing the long clearing times of high-AIC LVPCBs. Adopted in the 2014 NEC, expanded since.
  • LVPCB-LSI
  • Instantaneous trip (INST)
  • Incident energy (IE)
  • NFPA 70E
  • Zone-selective interlocking (ZSI)
  • ARMS / RELT (maintenance switching)
  • NEC 240.67
  • Differential relaying
NFPA 70EThe U.S. consensus standard for electrical-safety work practices, including the PPE category table and the requirement that arc-flash hazards be analyzed and labeled. NEC 110.16 references it for label content.
  • PPE category
  • Incident energy (IE)
  • Arc-flash boundary (AFB)
  • IEEE 1584
  • NEC 240.87
OSHA 1910.269OSHA's electrical safety regulation for electric power generation, transmission, and distribution. Cites NFPA 70E for general industry labels, energized-work permits, and PPE. The "compliance backbone" arc-flash labels rest on, even though the technical content is in NFPA 70E.
  • NFPA 70E
  • NEC 110.16
  • Arc rating
Per-unit methodA normalization scheme for power-system impedances. Pick a base MVA and base voltage; convert every transformer, cable, and source impedance into a dimensionless ratio relative to that base. Series impedances add as scalars; voltage-level transitions wash out automatically.
  • Bolted-fault current (Ibf)
  • X/R ratio
PPE categoryA 1–4 banding of incident-energy levels that maps to a prescribed clothing system per NFPA 70E. Higher categories require more layers of arc-rated fabric, ranging from a single arc-rated shirt-and-pants (Cat 1) to a full hood-equipped arc-flash suit (Cat 4).
  • Incident energy (IE)
  • Arc-flash boundary (AFB)
  • NFPA 70E
PPE category method (NFPA 70E)A table-driven shortcut for picking PPE that doesn't require an incident-energy study. Tables 130.7(C)(15)(a) and (b) prescribe a category based on equipment type and "task likelihood." Easier than an IE study; conservative for some equipment and dangerously under-conservative for others.
  • PPE category
  • Incident energy (IE)
  • NFPA 70E
Selective coordinationA protection-design property: at any fault current the system can deliver, only the device closest to the fault clears, leaving the rest of the system in service. Required by code for emergency, legally-required-standby, and elevator branches per NEC 700/701/620.
  • Time-current curve (TCC)
  • Short-time delay (S)
  • Instantaneous trip (INST)
  • LVPCB-LSI
  • Fuse class (RK5 / J / L / T)
Series reactorA deliberately-installed inductance in a feeder or bus tie used to limit available fault current at a downstream point. Common in industrial substations where raising transformer %Z would impair motor starting.
  • Bolted-fault current (Ibf)
  • X/R ratio
Short-time delay (S)On an LSI-equipped breaker, a deliberate hold-off time during higher fault currents to let a downstream device clear first. The "S" in LSI. Adjustable by both pickup multiple and delay time.
  • Time-current curve (TCC)
  • Long-time pickup (L)
  • Instantaneous trip (INST)
  • LVPCB-LSI
  • Selective coordination
Thermal-magnetic MCCBA Molded-Case Circuit Breaker with two trip elements: a thermal (bimetal) element for overload protection and a magnetic (electromagnet) element for instantaneous fault clearing. The default residential and light-commercial breaker. Limited adjustability — typically only the magnetic pickup, on commercial models.
  • Time-current curve (TCC)
  • Instantaneous trip (INST)
  • LVPCB-LSI
  • Fuse class (RK5 / J / L / T)
Time-current curve (TCC)A log-log plot of a protective device's clearing time as a function of current. Reading current on the X axis up to the curve gives the time the device takes to trip at that current.
  • Selective coordination
  • Instantaneous trip (INST)
  • Long-time pickup (L)
  • Short-time delay (S)
  • LVPCB-LSI
Working distance (WD)The distance from the prospective arc source to the worker's face and chest, where incident energy is evaluated. NFPA 70E standardizes WD by equipment class — 18 in for LV panelboards and MCCs, 24 in for LV switchgear, 36 in for MV switchgear.
  • Incident energy (IE)
  • Arc-flash boundary (AFB)
  • PPE category
X/R ratioThe ratio of reactance to resistance at a fault point, controlling how much DC offset and asymmetrical peak current appears in the first cycles of a fault. Higher X/R → larger asymmetric peak, longer-lived DC tail.
  • Bolted-fault current (Ibf)
Zone-selective interlocking (ZSI)A coordination scheme where each breaker asserts a signal output when its short-time element picks up, and reads inputs from breakers below. Upstream waits its full delay only if downstream is picked up; otherwise it trips with no intentional delay. Method 1 of NEC 240.87.
  • NEC 240.87
  • Selective coordination
  • Short-time delay (S)
  • ARMS / RELT (maintenance switching)
Tutorials TCC & Coordination Arc Flash & Short-Circuit Glossary

© 2026 Decisive Engineering LLC. All rights reserved. Client Login