Sandbox

Build a bus, sweep the scenario.

Two widgets, both editable. The first composes a short-circuit calculator above an arc-flash calculator — build a bus, the PPE category for that bus is computed live. The second is the TCC-bridge — drag the upstream LVPCB's settings and watch the arc-flash energy track its clearing time.

Educational tool only. Implements the IEEE 1584-2002 LV regression with simplified per-unit fault math. Outputs are not suitable for arc-flash labels, PPE selection, breaker rating, or any safety-critical engineering decision. Use a licensed production tool and consult a qualified protection engineer for any real-world arc-flash or coordination study.

1 · Scenario preset → topology → arc-flash label

Pick a named scenario to seed the one-line and arc-flash math, then pick a topology, pick the active bus, and see the short-circuit and arc-flash labels respond. On the double-ended diagram, the tie breaker is interactive — closing it parallels the two transformers and roughly doubles Isc at either bus, which the PPE category below tracks immediately.

Pass 4's canonical scenario: 500 MVA utility, 1500 kVA / 5.75 % transformer, 480 V switchgear at 24 in working distance, 200 ms clearing.

Topology

One-line diagram — preset: Default — 480 V commercial

Utility · 13.8 kV1500 kVA · 5.75 % Z480 V main busPanel APanel BPanel C

480 V main bus — short-circuit

Bolted Isc (sym)

29.8 kA

@ 480 V bus

X/R at bus

7.2

Asymmetrical peak

69.4 kA

half-cycle multiplier

Utility source (primary side)
Transformer

Arc-flash label (driven by linked Ibf above)

Incident energy 5.8 cal/cm²
Arc-flash boundary 70 in (1783 mm)
PPE Category 2

Arc-rated clothing min 8 cal/cm² — shirt + pants or coverall, hood, balaclava, gloves.

Arcing current

13.5 kA

≈ 54% of Ibf

Bolted Isc

25.0 kA

Clearing time

200 ms

Model

IEEE 1584-2002

System
Voltage 480 V
Grounding
IEEE 1584 model 1584-2002

Toggle pending — see the lesson note in L4.

Bolted fault current
Geometry
Electrode config Vertical in box (switchgear)
Gap between conductors 32 mm
Working distance 24 in
Clearing time

Includes device opening time. A 5-cycle breaker tripping instantaneously at 60 Hz ≈ 83 ms.

2 · Short-circuit → arc-flash label (no topology overhead)

Same linkage as above, just without the topology picker — useful when the bus shape is fixed and you only want to sweep the source impedance. Uncheck the link if you want to compare a what-if scenario without changing the bus.

Bus short-circuit (interactive)

Bolted Isc (sym)

29.8 kA

@ 480 V bus

X/R at bus

7.2

Asymmetrical peak

69.4 kA

half-cycle multiplier

Utility source (primary side)
Transformer

Arc-flash label (live from above)

Incident energy 5.8 cal/cm²
Arc-flash boundary 70 in (1783 mm)
PPE Category 2

Arc-rated clothing min 8 cal/cm² — shirt + pants or coverall, hood, balaclava, gloves.

Arcing current

13.5 kA

≈ 54% of Ibf

Bolted Isc

25.0 kA

Clearing time

200 ms

Model

IEEE 1584-2002

System
Voltage 480 V
Grounding
IEEE 1584 model 1584-2002

Toggle pending — see the lesson note in L4.

Bolted fault current
Geometry
Electrode config Vertical in box (switchgear)
Gap between conductors 32 mm
Working distance 24 in
Clearing time

Includes device opening time. A 5-cycle breaker tripping instantaneously at 60 Hz ≈ 83 ms.

3 · TCC bridge — clearing time linked to a real protective device

The upstream LVPCB's curve drives the clearing time on the arc-flash calc below. Drag the device's I pickup or S delay, watch the IE label move. Move the bus Isc slider to see how the same device behaves at different fault levels.

1101001k10k100k0.010.11101001kCurrent (A)Time (s)Upstream LVPCB curve + arc-flash energy1600 A main LVPCBBus Isc · 25.0 kA

The vertical line on the plot marks the fault current. The upstream device's curve at that current sets the clearing time below.

1600 A main LVPCB

Long-time (L)

Short-time (S)

Instantaneous (I)

Resulting arc-flash label

Incident energy 5.8 cal/cm²
Arc-flash boundary 70 in (1783 mm)
PPE Category 2

Arc-rated clothing min 8 cal/cm² — shirt + pants or coverall, hood, balaclava, gloves.

Arcing current

13.5 kA

≈ 54% of Ibf

Bolted Isc

25.0 kA

linked

Clearing time

200 ms

linked

Model

IEEE 1584-2002

System
Voltage 480 V
Grounding
IEEE 1584 model 1584-2002

Toggle pending — see the lesson note in L4.

Bolted fault current

Driven externally: 25.0 kA

Geometry
Electrode config Vertical in box (switchgear)
Gap between conductors 32 mm
Working distance 24 in
Clearing time

Driven externally: 200 ms