Module 2 · Arc Flash

The IEEE 1584 Model

Inputs (V, Isc, gap, electrode, WD, clearing time) → IE / AFB / PPE.

IEEE 1584 is an empirical regression — not first-principles physics. Researchers ran hundreds of staged arcing tests inside representative enclosures with calibrated calorimeters at known distances. The resulting equations predict the median incident energy a worker absorbs, given the system parameters.

The 2002 version (used in this calculator) covers 208 V – 15 kV with seven coefficients. The 2018 version refines the model with electrode-specific coefficients (so VCB, VCBB, and HCB give different energies even for the same Ibf and gap) and an enclosure-size correction. Production studies should use the 2018 model with vendor software that licenses it; the 2002 model is plenty for teaching the shape of the result.

You’ll see a Model toggle in the calculator below offering both versions. The 2018 option is disabled here — the coefficient table is published only in the licensed standard, and we don’t ship fabricated numbers. For real 2018-model output, run the scenario in SKM, ETAP, or EasyPower. The 2002 numbers here land within ~10–20 % of 2018 for typical LV / VCB configurations: fine for understanding the model’s shape, not for printing a real arc-flash label.

The seven inputs

InputWhy it matters
System voltageDrives the arcing current and sets which coefficient block applies. Higher V → more energy released per cycle.
Bolted IscThe bigger the available current, the bigger the arcing current that follows.
Conductor gapWider gap → longer arc → more voltage drop across the arc → more power.
Electrode configurationVCB / VCBB / HCB / VOA / HOA. Affects how much energy is reflected back at the worker (vs scattered into the box, vs going into open air).
Working distanceEnergy falls off with distance to some power x between 1.4 and 2.0. The exponent depends on equipment type.
Clearing timeThe arc burns for as long as the upstream device takes to interrupt. Energy is roughly proportional to time.
System groundingSolidly grounded systems tend to produce slightly less arcing-fault energy than ungrounded — the grounding path bleeds some current.

Try the calculator

480 V switchgear, bolted Isc 25 kA, 32 mm gap, 24 in working distance

Incident energy 5.8 cal/cm²
Arc-flash boundary 70 in (1783 mm)
PPE Category 2

Arc-rated clothing min 8 cal/cm² — shirt + pants or coverall, hood, balaclava, gloves.

Arcing current

13.5 kA

≈ 54% of Ibf

Bolted Isc

25.0 kA

Clearing time

200 ms

Model

IEEE 1584-2002

System
Voltage 480 V
Grounding
IEEE 1584 model 1584-2002

Toggle pending — see the lesson note in L4.

Bolted fault current
Geometry
Electrode config Vertical in box (switchgear)
Gap between conductors 32 mm
Working distance 24 in
Clearing time

Includes device opening time. A 5-cycle breaker tripping instantaneously at 60 Hz ≈ 83 ms.

The starting state — 480 V / 25 kA / 32 mm / VCB / 24 in / 200 ms — lands around 5.8 cal/cm², which puts you in PPE Category 2 territory: an arc-rated shirt-and-pants (or coverall) ensemble rated ≥ 8 cal/cm², not yet a full flash suit.

Try this — push each input

Clearing time is the lever

Drag t from 200 ms down to 50 ms (3 cycles). Energy drops by 4×. This is the most direct lever an engineer has — and it’s the bridge to the TCC coordination tutorial. Every short-time-delay reduction or instantaneous-trip enable on the upstream device reduces the worker’s incident energy proportionally.

Now push t up to 1 s and the energy reaches ~29 cal/cm² — Cat 4, the top of the PPE scale. Push it on toward 1.5 s and you cross into DANGER territory — no PPE category exists at that level, and energized work isn’t permitted without engineering reduction.

A 1-second clearing time isn’t hypothetical. It’s what you get when:

That combination, perfectly common in older industrial installations, produces lethal arc-flash energies at the bus.

Electrode geometry matters

Switch from VCB (vertical-in-box, like switchgear) to VOA (vertical open air). Energy at the worker drops a little — open-air arcs aren’t reflected back at you by the enclosure walls. But the arc-flash boundary distance grows, because energy radiates outward unimpeded. Open-air arcs are more dangerous to bystanders even though they’re slightly less dangerous to the worker right in front.

Working distance and the inverse-square (-ish)

Switch working distance from 18 in to 36 in. For switchgear, the distance exponent x is 1.473 — so doubling distance reduces energy by 2^1.473 ≈ 2.8×. Not quite inverse-square, but close.

The arc-flash boundary in the label answer is the distance at which incident energy drops to 1.2 cal/cm² — roughly the threshold for second-degree skin burns. If you can stand outside that boundary, you don’t need arc-rated clothing for the task.

Big current isn’t always the worst-case

Drop Ibf from 25 kA down to 5 kA. Counter-intuitively, energy doesn’t drop linearly — and the arcing current as a fraction of Ibf grows at low Ibf. A 5 kA fault with a slow clearing time can deliver as much energy as a 25 kA fault with a fast one. The relationship is nonlinear because:

  1. Arcing current drops sub-linearly with Ibf.
  2. The breaker’s clearing time often grows at lower Ibf (you’re walking down its time-current curve into the slow region).

Together these two effects can make moderate fault currents the worst-case for arc-flash, even though they’re not the worst case for breaker AIC or bus bracing. Many real coordination studies find their worst-case incident energy at a current 30–50 % of Ibf.

The two outputs that matter

The label answer has two numbers a worker actually uses:

  • Incident energy at working distance (cal/cm²) — sets the arc-rating of the PPE the worker has to be wearing.
  • Arc-flash boundary (in or mm) — sets the distance at which any other person needs the same PPE or needs to be physically excluded by barriers.

Once you’ve calculated the incident energy, NFPA 70E’s incident-energy analysis method (130.5(G)) has the worker wear clothing and PPE rated for at least that many cal/cm². The familiar PPE categories come from a separate method (Table 130.7(C)(15)) — the next lesson walks through both, and the rule that you don’t mix them.

What’s next

Lesson 5 turns the same calculator’s output into the label that goes on the equipment door. Categories, boundaries, working distance assumptions — and what to do when the answer is DANGER.